成熟人妻AV无码专区_人人添人人妻人人爽夜欢视AV_亚洲AV无一区二区三区_亚洲 A V无 码免 费 成 人 A V

業務聯系

上海鴻唯電源系統有限公司

聯系人:黃建喜

聯系電話:

郵箱:

傳真號碼:

地址:上(shang)海市寶山城市工業園區城銀(yin)路318號7幢F區

UPS蓄電池如何安裝?

  UPS蓄(xu)電(dian)(dian)池如(ru)何安(an)裝(zhuang)?下(xia)面由鴻唯電(dian)(dian)源(yuan)來給大家介紹下(xia)。UPS電(dian)(dian)池也有(you)鉛酸(suan)電(dian)(dian)池。安(an)裝(zhuang)時應注意(yi)以下(xia)事項(xiang),避免因充電(dian)(dian)而引起的(de)錯誤。鴻唯電(dian)(dian)源(yuan)總(zong)結了常用的(de)安(an)裝(zhuang)方(fang)(fang)法,可以根據(ju)(ju)不(bu)同的(de)設備型號和不(bu)同的(de)地方(fang)(fang)進行安(an)裝(zhuang)。根據(ju)(ju)我們的(de)電(dian)(dian)池安(an)裝(zhuang)程序,安(an)全地卸(xie)下(xia)舊(jiu)的(de)UPS電(dian)(dian)池并安(an)裝(zhuang)新(xin)的(de)電(dian)(dian)池。

  UPS蓄(xu)電(dian)池安(an)裝(zhuang)方法(fa)與步驟如(ru)下:

  1、將發電(dian)(dian)機(ji)輸出線(xian)插入備用電(dian)(dian)源連接器(qi),然(ran)后啟動。讓發電(dian)(dian)機(ji)運行一段時(shi)間。

  2、打開電(dian)(dian)池柜(ju),找到(dao)連接UPS電(dian)(dian)源(yuan)主機的(de)輸出線,確認正負(fu)極。

  3、確認發(fa)電機穩定運(yun)行。待配電柜轉(zhuan)換(huan)開關輸入端測得電壓正常后,將開關轉(zhuan)到發(fa)電機側,觀察(cha)確認ups電池(chi)主機運(yun)行正常,斷開ups電池(chi)柜的電池(chi)空氣開關。

  4、準備拆(chai)除舊(jiu)的(de)UPS電(dian)池。電(dian)池架上的(de)電(dian)池從上到下取出。拆(chai)下螺釘(ding)后,用電(dian)工(gong)膠帶(dai)將連接(jie)線的(de)接(jie)頭包好,并做好絕緣工(gong)作。請注意,這(zhe)一步非常重要。不要偷(tou)懶,防止短路電(dian)流(liu)產生(sheng)的(de)正負(fu)極接(jie)觸短路,并有觸電(dian)的(de)危險。

  5、卸下(xia)所有UPS電池,放置好,然后開始安裝(zhuang)新電池。

  6、根(gen)據電池編號(hao),從第一層開始安裝,從電池架的(de)底(di)層開始安裝。位(wei)置和(he)方向與拆下的(de)舊蓄電池相同。連(lian)接器螺絲必須(xu)(xu)擰緊(jin),連(lian)接線必須(xu)(xu)整齊,電池之間(jian)應(ying)有適(shi)當的(de)間(jian)隙。連(lian)接過程應(ying)至(zhi)少為25 mm,以防短路。

  7、ups電池(chi)安裝后,確認正負(fu)極連(lian)(lian)接正確,測量總電壓,確認電池(chi)安裝連(lian)(lian)接正確。

  8、根據電(dian)(dian)池參數(shu),計算充(chong)電(dian)(dian)電(dian)(dian)壓,測量ups輸(shu)出充(chong)電(dian)(dian)電(dian)(dian)壓,滿足該批電(dian)(dian)池的充(chong)電(dian)(dian)要求。關閉(bi)電(dian)(dian)池柜,打開(kai)空氣,查(cha)看(kan)主機充(chong)電(dian)(dian)菜(cai)單,電(dian)(dian)池處于充(chong)電(dian)(dian)狀態。

  9、安裝UPS電(dian)(dian)源(yuan)(yuan)電(dian)(dian)池(chi)柜,將UPS主(zhu)機輸(shu)入電(dian)(dian)源(yuan)(yuan)切換回市電(dian)(dian),確認(ren)UPS主(zhu)機輸(shu)入輸(shu)出電(dian)(dian)壓正常。停止(zhi)發電(dian)(dian)機,拆(chai)下連(lian)接線,收(shou)拾好工具,裝上舊(jiu)的(de)UPS電(dian)(dian)池(chi),準備運回,清理現場。

  UPS電(dian)池組安裝有哪些要求?

  1、UPS電(dian)池組的平臺、機架及間距應符合設(she)計要(yao)求;

  2、UPS電池安裝平(ping)整(zheng),間距均勻,同一(yi)排(pai)(pai)、同一(yi)列的(de)電池箱高度一(yi)致,排(pai)(pai)列整(zheng)齊(qi);

  3、.連接(jie)條與絲錐連接(jie)正(zheng)確,接(jie)頭處涂電工(gong)復合(he)脂,螺栓緊固;

  4、有抗震要(yao)求時,抗震設施應符合有關(guan)規定,牢固可靠;

  5、溫度(du)計、密度(du)計和液位線應(ying)位于便于檢查的一(yi)側。

  以上(shang)為UPS蓄電(dian)(dian)(dian)池(chi)(chi)更(geng)換(huan)方法及安(an)裝步(bu)驟(zou)。原則(ze)(ze)上(shang),如(ru)果UPS蓄電(dian)(dian)(dian)池(chi)(chi)中的電(dian)(dian)(dian)池(chi)(chi)使用時間不足(zu)三年,則(ze)(ze)只(zhi)需(xu)更(geng)換(huan)壞電(dian)(dian)(dian)池(chi)(chi)即可。如(ru)果電(dian)(dian)(dian)池(chi)(chi)已使用三年或以上(shang),則(ze)(ze)需(xu)要更(geng)換(huan)整個UPS蓄電(dian)(dian)(dian)池(chi)(chi)。由(you)專業UPS主控安(an)裝UPS電(dian)(dian)(dian)池(chi)(chi)更(geng)安(an)全。


上一篇:利用閥控密封鉛酸蓄電池內阻(或電導)的變化去在線檢測電池的容量和預測電池壽命

下一篇:沒有了!

客戶服務熱線

座機:

電話:

QQ/郵(you)箱(xiang):308237334

在(zai)線客服